LLT125-5/4 is a vertical cooling-tower circulation pump from the CNP LLT (coaxial) range (50 Hz). Rated 4 kW, 120–200 m³/h, head 3–7 m. Net weight 83 kg.

  • Large flow, low head: 30–300 m³/h, up to 8.9 m
  • Liquid temperature -15 to +100 °C, working pressure up to 6 bar
  • Coaxial structure, small footprint, in-line DN65–DN150 flanges

Performance curve Curve-based

0246805115225Flow Q (m³/h)Head H (m)LLT125-5/4: Q 12 m³/h, H 6.5 mLLT125-5/4: Q 13 m³/h, H 6.1 mLLT125-5/4: Q 14 m³/h, H 5.7 mLLT125-5/4: Q 15 m³/h, H 5.2 mLLT125-5/4: Q 16 m³/h, H 5 mLLT125-5/4: Q 17 m³/h, H 4.3 mLLT125-5/4: Q 18 m³/h, H 4.1 mLLT125-5/4: Q 19 m³/h, H 3.7 mLLT125-5/4: Q 2 m³/h, H 2.7 m

Efficiency, shaft power and NPSHr are not published for this model in the source catalogue.

Head versus flow at 50 Hz, 1450 rpm, clean water. Source: Performance table and installation dimensions, printed pp. 9-10.

Flow (m³/h)Head (m)
1206.5
1306.1
1405.7
1505.2
1605
1704.3
1804.1
1903.7
2002.7

Dimensions & weight

B2 = 195B1 = 145H = 731Net weight: 83 kg
Outline drawn in proportion to this model's catalogue dimensions (simplified, only the labelled dimensions are shown). Codes match the table; confirm against the approved CNP drawing before installation.
CodeDescriptionValue
Apump length560 mm
B1lower section height: base to motor flange145 mm
B2upper section height: motor195 mm
Hoverall height731 mm
A1mounting200 mm
A2mounting240 mm
d1mounting hole15 mm
H1inlet axis height170 mm
H2H2140 mm
H3H330 mm
DNinlet / outlet flange125 mm
dflange inner bolt circle184 mm
Kbolt circle210 mm
Dflange outer diameter250 mm
alphaα — bolt angle (°)22.5 mm
boltsNumber of flange bolts8 mm
bolt_diaBolt hole diameter18 mm
—Net weight83 kg

Need a pump or a spare part?

Send us the flow and head you need, or the model code and nameplate details of the pump you are repairing. Our team replies with a quotation.