CNPPumps PakistanHESPAK Pvt. Ltd. Quote list0 Get a Quote
Vertical cooling-tower circulation pump

LLT65-5/1.1

LLT (coaxial) · 50 Hz

LLT65-5/1.1 is a vertical cooling-tower circulation pump from the CNP LLT (coaxial) range (50 Hz). Rated 1.1 kW, 30–50 m³/h, head 3–7 m. Net weight 32 kg.

  • Large flow, low head: 30–300 m³/h, up to 8.9 m
  • Liquid temperature -15 to +100 °C, working pressure up to 6 bar
  • Coaxial structure, small footprint, in-line DN65–DN150 flanges

Performance curve Curve-based

024680246Flow Q (m³/h)Head H (m)LLT65-5/1.1: Q 3 m³/h, H 6.6 mLLT65-5/1.1: Q 35 m³/h, H 5.9 mLLT65-5/1.1: Q 4 m³/h, H 5 mLLT65-5/1.1: Q 45 m³/h, H 4.3 mLLT65-5/1.1: Q 5 m³/h, H 3.1 m

Efficiency, shaft power and NPSHr are not published for this model in the source catalogue.

Head versus flow at 50 Hz, 2900 rpm, clean water. Source: Performance table and installation dimensions, printed pp. 5-6.

Flow (m³/h)Head (m)
306.6
355.9
405
454.3
503.1

Dimensions & weight

B2 = 110B1 = 100H = 490Net weight: 32 kg
Outline drawn in proportion to this model's catalogue dimensions (simplified, only the labelled dimensions are shown). Codes match the table; confirm against the approved CNP drawing before installation.
CodeDescriptionValue
Apump length340 mm
B1lower section height: base to motor flange100 mm
B2upper section height: motor110 mm
Hoverall height490 mm
A1mounting130 mm
A2mounting170 mm
d1mounting hole15 mm
H1inlet axis height100 mm
H2H2105 mm
H3H312 mm
DNinlet / outlet flange65 mm
dflange inner bolt circle118 mm
Kbolt circle145 mm
Dflange outer diameter185 mm
alphaα — bolt angle (°)45 mm
boltsNumber of flange bolts4 mm
bolt_diaBolt hole diameter18 mm
—Net weight32 kg

Need a pump or a spare part?