CNPPumps PakistanHESPAK Pvt. Ltd. Quote list0 Get a Quote
In-line single-stage circulation pump

TD80-81/2

TD (in-line circulation) · 60 Hz

TD80-81/2 is an in-line single-stage circulation pump from the CNP TD (in-line circulation) range (60 Hz). Rated 37 kW, 5–100 m³/h, head 78–82 m. Net weight 338 kg.

  • Eleven sizes, DN32 to DN300, flow up to about 900 m³/h
  • Head up to about 100 m, 2-pole and 4-pole motors
  • Liquid from -15 to +110 °C, working pressure 12 bar (16 bar special)

Performance curve Curve-based

0246810255751125Flow Q (m³/h)Head H (m)TD80-81/2: Q 5 m³/h, H 81.9 mTD80-81/2: Q 1 m³/h, H 82.1 mTD80-81/2: Q 2 m³/h, H 82.8 mTD80-81/2: Q 3 m³/h, H 82.9 mTD80-81/2: Q 4 m³/h, H 82.9 mTD80-81/2: Q 5 m³/h, H 82.7 mTD80-81/2: Q 6 m³/h, H 82.5 mTD80-81/2: Q 7 m³/h, H 82.4 mTD80-81/2: Q 8 m³/h, H 81 mTD80-81/2: Q 9 m³/h, H 80 mTD80-81/2: Q 1 m³/h, H 78 m

Efficiency, shaft power and NPSHr are not published for this model in the source catalogue.

Head versus flow at 60 Hz, 3500 rpm, clean water. Source: Performance table, PDF p. 31.

Flow (m³/h)Head (m)
581.9
1082.1
2082.8
3082.9
4082.9
5082.7
6082.5
7082.4
8081
9080
10078

Dimensions & weight

Dimension codes in the table refer to the catalogue drawing.
CodeDescriptionValue
DD400 mm
B1B1400 mm
B2B2310 mm
B3B3182 mm
B4B4163 mm
B5B5144 mm
H1H1115 mm
H2H2279 mm
H3H31044 mm
L1L1500 mm
L2L2250 mm
—Net weight338 kg

Need a pump or a spare part?

Send us the flow and head you need, or the model code and nameplate details of the pump you are repairing. Our team replies with a quotation.